| 220.1 | 120.1 | Scope | Scope of the load calculation article. Informational Note 120.1 carries a figure showing the new layout. | ConfirmedECM |
| 220.3 | Table 120.4 | Specific purpose calculations | References to calculation rules that sit outside the article, such as fixed resistance heaters at 425.4. Became a table. | ConfirmedECM |
| 220.5(A) | 120.5(A) | Standard voltages | Unchanged. Use the standard voltages unless another is specified. | ConfirmedECM |
| 220.5(B) | 120.5(B) | Rounding | Unchanged. Fractions of an ampere round to whole amperes. | ConfirmedECM |
| 220.5(C) | 120.5(C) | Floor area | Outside dimensions, excluding open porches and similar. 2026 confirms non habitable detached structures stay out. | ConfirmedECM |
| 220.5 | 120.5(D) | DC equivalent | Use VA in place of watts for direct current loads. | ConfirmedECM |
| 220.5 | 120.5(E) | Continuous loads | NEW statement. Load calculations are not required to apply the 125 percent multiplier. It still applies to conductor and OCPD sizing. | ConfirmedECM |
| 220.60 | 120.6 | Noncoincident loads | Simplified. Only the single largest of the loads that cannot run together goes in the total. | ConfirmedECM |
| Article 750 | 120.7 | Power control systems | NEW. PCS recognised in its own right. 120.7(A) requires compliance with Article 130, Part II. The PCS setpoint counts as a continuous load. | ConfirmedECM |
| 220.10 | 120.10 | Index to the article | The pointer section telling you where each load type lives. | Pattern |
| 220.12 | 120.12 | General lighting, non dwelling | Unit loads by occupancy. Table 220.12 became Table 120.12. | ConfirmedKeentel |
| (new) | 120.13 | Branch circuit load, dwelling | NEW section. Branch circuit quantity for a dwelling still uses 3 VA per square foot, so lowering 120.41 does not reduce the circuit count. | ConfirmedECM |
| 220.14 | 120.14 | Specific branch circuit loads | Outlet and specific equipment loads. Dryers keep the 5,000 VA minimum. The 180 VA per receptacle rule for non dwellings sits at 120.14(I). | ConfirmedKopperfield |
| 220.52 | 120.52 | Small appliance and laundry | Unchanged. 1,500 VA for each 20 A small appliance and laundry branch circuit. | Pattern |
| 220.40 | 120.40 | Feeder and service, general | The general requirement that the calculated load is not less than the sum of the branch circuit loads. | Pattern |
| 220.41 | 120.41 | Dwelling unit, minimum unit load | CHANGED. 3 VA per square foot became 2 VA per square foot for feeder and service calculations. A 33 percent cut. | ConfirmedECM |
| 220.42 | 120.42 | General lighting by occupancy | Non dwelling unit loads. Table 220.42(A) became Table 120.42(A). | Pattern |
| 220.44 | 120.44 | Receptacle loads, non dwelling | The demand factor applied to non dwelling receptacle load. Easy to forget and it is still here. | Pattern |
| 220.45 | 120.45 | Lighting demand factors | Unchanged in substance. First 3,000 VA at 100 percent, up to 120,000 at 35 percent, remainder at 25 percent. | ConfirmedThe Electric Times |
| 220.50 | 120.50 | Motors | Motor loads, routing to 430.24 and 430.25 for the sizing basis. The 25 percent largest motor adder lives here. | Pattern |
| 220.53 | 120.53 | Appliance demand factors | Conceptually unchanged. 75 percent where four or more appliances of 1/4 hp or 500 W and above are present. | ConfirmedKopperfield |
| 220.54 | 120.54 | Electric clothes dryers | CHANGED. Table simplified. Three and four dryers fell from 100 percent to 80 percent, and five fell from 85 to 80. | ConfirmedNFPA errata |
| 220.55 | 120.55 | Ranges and cooking appliances | Unchanged. Columns A, B and C, with Note 1 adding 5 percent per kW above 12. | Confirmednecmastery |
| 220.56 | 120.56 | Kitchen equipment | EXPANDED. Now takes in instantaneous electric water heaters alongside commercial kitchen equipment, so they qualify for demand factor treatment. | ConfirmedKopperfield |
| 220.57 | 120.57 | Electric vehicle supply equipment | CHANGED. Was the larger of 7,200 VA or nameplate. Now the nameplate rating where it is known, otherwise 7,200 VA. Calculated at 100 percent, not 125. | ConfirmedMike Holt |
| 220.61 | 120.61 | Neutral load | Feeder and service neutral, including the 70 percent reduction on the portion above 200 A. | Pattern |
| 220.82 | 120.82 | Optional method, dwelling unit | CHANGED. First tier fell from 10 kVA to 8 kVA at 100 percent. Remainder still 40 percent. | ConfirmedECM |
| (new) | 120.82(D) | Optional method, EVSE | NEW. EVSE is calculated at 100 percent on top of the tiered load instead of being run through the 40 percent remainder. | ConfirmedMike Holt |
| 220.83 | 120.83 | Existing dwelling unit | CHANGED. Multi table structure replaced by one table. New load demand factors added: new EVSE 80 percent, new central electric resistance heat 80 percent, all other new load 50 percent. | ConfirmedMike Holt |
| 220.84 | 120.84 | Optional, multifamily | Optional calculation for a multifamily dwelling. | Pattern |
| 220.85 | 120.85 | Two dwelling units | Where two dwelling units are supplied by one feeder or service. | Pattern |
| 220.86 | 120.86 | Optional, schools | Optional calculation for school buildings. | Pattern |
| 220.87 | 120.87 | Existing loads | CHANGED. Loads being removed may now be subtracted when you evaluate whether new load fits. | Confirmedtrueloadapp |
| 220.88 | 120.88 | Optional, new restaurants | Optional calculation for new restaurants. | Pattern |
| 220.100 | 120.100 | Farm loads, general | Part covering farm load calculations. | Pattern |
| 220.102 | 120.102 | Farm, individual buildings | | Pattern |
| 220.103 | 120.103 | Farm, total load | | Pattern |
| 220.110 | 120.110 | Health care, receptacles | Demand factors brought in from Article 517 in the 2023 reorganisation. | Pattern |
| 220.120 | 120.120 | Marinas and docking facilities | Demand factors brought in from Article 555 in the 2023 reorganisation. | Pattern |